Application Example
During a “Switch-OnTo-Fault” condition, the User is usually requested to make the embedded protective function 
tripping of the faulted line faster, instantaneous, or sometimes non-directional.
Such a “Switch-OnTo-Fault” application can easily be realized using the 
Adaptive Parameter
 features mentioned 
previously.  The standard time overcurrent protection element (e.g.: 51P) should trip instantaneously in case of 
SOTF 
condition,.  If the 
SOTF
 logic function »SOTF ENABLED« is detecting a manual breaker close condition, the relay switches 
to 
Adaptive Set 1
 if the signal »SOTF.ENABLED« is assigned to 
Adaptive Set 1
.  The corresponding 
Adaptive Set 1
 will 
become active and than »
t = 0«
 sec.