EMR-4000 IM02602009E
Use the start delay to block tripping until the load stabilizes after a start. Use run delays to avoid nuisance alarms or
trips for load transients.
To configure this function for operation under an alarm condition, the User must assign the functions pickup ( for
example 50J[1].Pickup) to an output relay, under >>Device Parm / Relay Outs<< that the User has identified as the
Alarm relay output. Likewise, to illuminate an LED under a functions alarm condition, LED 2 must be assigned the
functions pickup. Several elements are configure as such at the factory for convenience.
www.eaton.com 481