EMR-4000 IM02602009E
Device Planning Parameters of the Reactive Power Protection Module
Parameter Description Options Default Menu path
Mode Mode Do not use,
Over forward,
Over reverse,
Under forward,
Under reverse
32V[1]: Over
forward
32V[2]: Under
forward
32V[3]: Over
reverse
[Device Planning]
Global Protection Parameters of the Reactive Power Protection Module
Parameter Description Setting range Default Menu path
ExBlo1 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Power-Prot
/32V[1]]
ExBlo2 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Power-Prot
/32V[1]]
ExBlo TripCmd External blocking of the Trip Command of the module/the
element, if blocking is activated (allowed) within a
parameter set and if the state of the assigned signal is
true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Power-Prot
/32V[1]]