EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
WD 4 Trip Function Winding 4 Trip Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 4]
WD 4 Alarm Winding 4 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 4]
WD 4 t-Delay Winding 4 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min 1min [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 4]
WD 4 Trip Winding 4 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C 100°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 4]
WD 5 Alarm
Function
Winding 5 Alarm Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 5]
WD 5 Trip Function Winding 5 Trip Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 5]
WD 5 Alarm Winding 5 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 5]