EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
MB 1 Alarm
Function
Motor Bearing 1 Alarm Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 1]
MB 1 Trip Function Motor Bearing 1 Trip Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 1]
MB 1 Alarm Motor Bearing 1 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 1]
MB 1 t-Delay Motor Bearing 1 If this time is expired a Temperature
Alarm will be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min 1min [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 1]
MB 1 Trip Motor Bearing 1 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C 100°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 1]
MB 2 Alarm
Function
Motor Bearing 2 Alarm Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 2]
MB 2 Trip Function Motor Bearing 2 Trip Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 2]
www.eaton.com 721