EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
Aux Trip Auxiliary Threshold for Temperature Trip
Only available if: Device Planning: Aux = Use
0 - 200°C 100°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux Group]
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
Voting 1 Voting: This parameter defines how many of the selected
channels must be over its threshold level for getting a
voting trip
1 - 12 1 [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
WD 1 Winding 1 No,
Yes
Yes [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
WD 2 Winding 2 No,
Yes
Yes [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
WD 3 Winding 3 No,
Yes
Yes [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
WD 4 Winding 4 No,
Yes
Yes [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
www.eaton.com 728