EMR-4000 IM02602009E
Wiring RTDs to the URTDII Module
RTD Control URTDII Connection
Name
Terminals Transformer Temperature Monitoring
Point
RTD1:
Alarm Functional
Trip Functional
W1-A Alarm
W1-A t-Delay
W1-A Trip
MW1 J2-1, J2-2 W1-A – Transformer Winding 1,
Phase A RTD Temperature.
RTD2:
Alarm Functional
Trip Functional
W1-B Alarm
W1-B t-Delay
W1-B Trip
MW2 J2-5, J2-6 W1-B - Transformer Winding 1,
Phase B RTD Temperature.
RTD3:
Alarm Functional
Trip Functional
W1-C Alarm
W1-C t-Delay
W1-C Trip
MW3 J2-8, J2-9 W1-C - Transformer Winding 1,
Phase C RTD Temperature.
RTD4:
Alarm Functional
Trip Functional
W2-A Alarm
W2-A t-Delay
W2-A Trip
MW4 J2-12, J2-13 W2-A - Transformer Winding 2,
Phase A RTD Temperature.
RTD5:
Alarm Functional
Trip Functional
W2-B Alarm
W2-B t-Delay
W2-B Trip
MW5 J2-15, J2-16 W2-B - Transformer Winding 2,
Phase B RTD Temperature.
RTD6:
Alarm Functional
Trip Functional
W2-C Alarm
W2-C t-Delay
W2-C Trip
MW6 J2-19, J2-20 W2-C - Transformer Winding 2,
Phase C RTD Temperature.
RTD7:
Alarm Functional
Trip Functional
Amb1 Alarm
Amb1 t-Delay
Amb1 Trip
MB1 J10B-19, J10B-20 AMB1 - Transformer Ambient RTD
Temperature (1).
www.eaton.com 742