EMR-4000 IM02602009E
Global Protection Parameters of the Trip Circuit Monitoring Module
Parameter Description Setting range Default Menu path
Mode Select if trip circuit is going to be monitored when the
breaker is closed or when the breaker is either open or
close.
Closed,
Either
Closed [Protection Para
/Global Prot Para
/Supervision
/TCM]
Input 1 Select the input configured to monitor the trip coil when
the breaker is closed.
1..n, Dig Inputs DI-8P X1.DI 1 [Protection Para
/Global Prot Para
/Supervision
/TCM]
Input 2 Select the input configured to monitor the trip coil when
the breaker is open. Only available if Mode set to
“Either”.
Only available if: Mode = Either
1..n, Dig Inputs -.- [Protection Para
/Global Prot Para
/Supervision
/TCM]
ExBlo1 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Supervision
/TCM]
ExBlo2 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Supervision
/TCM]
www.eaton.com 796