EMR-4000 IM02602009E
Name Description
MStart.Start Pickup Signal: Pickup
MStart.Trip Signal: Trip
MStart.TripCmd Signal: Trip Command
MStart.Stop Signal: Motor is in stop mode
MStart.Start Signal: Motor is in start mode
MStart.Run Signal: Motor is in run mode
MStart.Blo Signal: Motor is blocked for starting or transition to Run mode
MStart.I_Transit Signal: Current transition signal
MStart.T_Transit Signal: Time transition signal
MStart.NOCSBlocked Signal: Motor is prohibited to start due to number of cold start limits
MStart.SPHBlocked Signal: Motor is prohibited to start due to starts per hour limits
MStart.SPHBlockAlarm Signal: Motor is prohibited to start due to starts per hour limits, would come active in the next stop
MStart.TBSBlocked Signal: Motor is prohibited to start due to time between starts limits
MStart.ThermalBlock Signal: Thermal block
MStart.RemBlockStart Signal: Motor is prohibited to start due to external blocking through digital input DI
MStart.TransitionTrip Signal: Start transition fail trip
MStart.ZSSTrip Signal: Zero speed trip (possible locked rotor)
MStart.INSQSP2STFaill Signal: Fail to transit from stop to start based on reported back time
MStart.INSQSt2RunFail Signal: Fail to transit from start to run based on reported back time
MStart.LATBlock Signal: Long acceleration timer enforced
MStart.ColdStartSeq Signal: Motor cold start sequence flag
MStart.ForcedStart Signal: Motor being forced to start
MStart.TripPhaseReverse Signal: Relay tripped because of phase reverse detection
MStart.EmergOverrideDI Signal: Emergency override start blocking through digital input DI
MStart.EmergOverrideUI Signal: Emergency override start blocking through front panel
MStart.ABKActive Signal: Anti-backspin is active. For certain applications, such as pumping a fluid up a pipe, the motor may be
driven backward for a period of time after it stops. The anti-backspin timer prevents starting the motor while it
is spinning in the reverse direction.
MStart.MotorStopBlo Signal: Motor stop block other protection functions
50P[1].Pickup Signal: Pickup
50P[1].Trip Signal: Trip
50P[1].TripCmd Signal: Trip Command
50P[2].Pickup Signal: Pickup
50P[2].Trip Signal: Trip
50P[2].TripCmd Signal: Trip Command
50P[3].Pickup Signal: Pickup
50P[3].Trip Signal: Trip
50P[3].TripCmd Signal: Trip Command
www.eaton.com 812