EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
Angle VC Fund. Start Position respectively Start Angle of the Voltage
Phasor during Pre Phase:Phase C
-360 - 360° 120° [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/VT]
Angle VX meas
Fund.
Start Position respectively Start Angle of the Voltage
Phasor during Pre Phase: VX
-360 - 360° [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/VT]
VA Fund. Voltage Fundamental Magnitude in Fault State: Phase A 0.00 - 1.30Vn 0.29Vn [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/FaultSimulation
/VT]
VB Fund. Voltage Fundamental Magnitude in Fault State: Phase B 0.00 - 1.30Vn 0.29Vn [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/FaultSimulation
/VT]
www.eaton.com 856