EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
Force RO2 By means of this function the normal Relay Output State
can be overwritten (forced). The relay can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Normal,
De-Energized,
Energized
Normal [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4Z X2]
Force RO3 By means of this function the normal Relay Output State
can be overwritten (forced). The relay can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Normal,
De-Energized,
Energized
Normal [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4Z X2]
Force RO4 By means of this function the normal Relay Output State
can be overwritten (forced). The relay can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Normal,
De-Energized,
Energized
Normal [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4Z X2]