EMR-4000 IM02602009E
Name Description
MStart.JamStartBlock Signal: JAM Start Delay. JAM(Instantaneous Overcurrent) elements are blocked for the time programmed
under this parameter
MStart.UnbalStartBlock Signal: Motor start block current unbalance signal
MStart.Blo-Generic1 Generic Start Delay. This value can be used to block any protective element.1
MStart.Blo-Generic2 Generic Start Delay. This value can be used to block any protective element.2
MStart.Blo-Generic3 Generic Start Delay. This value can be used to block any protective element.3
MStart.Blo-Generic4 Generic Start Delay. This value can be used to block any protective element.4
MStart.Blo-Generic5 Generic Start Delay. This value can be used to block any protective element.5
MStart.I_Transit Signal: Current transition signal
MStart.T_Transit Signal: Time transition signal
MStart.MotorStopBlo Signal: Motor stop block other protection functions
MStart.RFD_IA_Normal Signal: System IA RotaryFieldDetection Normal
MStart.RFD_IA_Reverse Signal: System IA RotaryFieldDetection Reverse
MStart.VUnbalStartBlock Signal: Motor start block voltage unbalance signal.
MStart.UnderVStartBlock Signal: Undervoltage Start Delay. Undervoltage elements are blocked for the time programmed under this
parameter
MStart.OverVStartBlock Signal: Overvoltage Start Delay. Overvoltage elements are blocked for the time programmed under this
parameter
MStart.PowerStartBlock Signal: Power Start Delay. Power elements are blocked for the time programmed under this parameter
MStart.PFacStartBlock Signal: Power Factor Start Delay. Power Factor elements are blocked for the time programmed under this
parameter
MStart.FrqStartBlock Signal: Frequency Start Delay. Frequency elements are blocked for the time programmed under this
parameter
MStart.RemStartBlock-I State of the module input: Remote Motor Start Blocking
MStart.EmgOvr-I State of the module input: Emergency Override. Signal has to be active in order to release the thermal
capacity of the motor. Please notice that by doing this you run the risk of damaging the motor. “EMGOVR” has
to be set to “DI” or “DI or UI” for this input to take effect
MStart.INSQ-I State of the module input: INcomplete SeQuence
MStart.ZSS-I State of the module input: Zero Speed Switch
MStart.STPC Blo-I State of the module input: With this setting a Digital Input keeps the Motor in the RUN mode, even when the
motor current drops below STPC (motor stop current).
50P[1].Active Signal: Active
50P[1].ExBlo Signal: External Blocking
50P[1].Rvs Blo Signal: Reverse Blocking
50P[1].Blo TripCmd Signal: Trip Command blocked
50P[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
50P[1].Pickup IA Signal: Pickup IA
50P[1].Pickup IB Signal: Pickup IB
50P[1].Pickup IC Signal: Pickup IC
50P[1].Pickup Signal: Pickup