Installation Requirements
30 H-Max Series Adjustable Frequency Drive    MN04008005E—September 2011    
EMC Installation
The responsibility to comply with the legally stipulated limit 
values and thus the provision of electromagnetic 
compatibility is the responsibility of the end user or system 
operator. This operator must also take measures to minimize 
or remove emissions in the environment concerned (see 
figure on Page 5). He must also use means to increase the 
interference immunity of the system devices.
In a drive system (PDS) with frequency inverters, you should 
take measures for electromagnetic compatibility (EMC) while 
doing your planning, because changes or improvements to 
the installation site, which are required in the installation or 
while mounting, are normally associated with additional 
higher costs.
The technology and system of a frequency inverter cause the 
flow of high frequency leakage current during operation. All 
grounding measures must therefore be implemented with 
low impedance connections over a large surface area.
With leakage currents greater than 3.5 mA, in accordance 
with VDE 0160 or EN 60335, either
●
the protective conductor must have a cross-section 
10 mm
2
●
the protective conductor must be open-circuit monitored, 
or
●
the second protective conductor must be fitted
For an EMC-compliant installation, we recommend the 
following measures:
●
Installation of the frequency inverter in a metallic, 
electrically conducting enclosure with a good connection 
to earth
●
Shielded motor cables (short cable lengths)
Ground all conductive components and housings in a drive 
system using as short a line as possible with the greatest 
possible cross-section (Cu-braid).
EMC Measures in the Control Panel
For EMC-compatible installation, connect all metallic parts of 
the device and the switching cabinet together over broad 
surfaces and so that high-frequencies will be conducted. 
Mounting plates and cabinet doors should make good 
contact and be connected with short HF-braided cables. 
Avoid using painted surfaces (anodized, chromized). An 
overview of all EMC measures is provided in the figure on 
Page 31.
Install the frequency inverter as directly as possible (without 
spacers) on a metal plate (mounting plate).
Route input and motor cables in the switch cabinet as close 
to the ground potential as possible. This is because free 
moving cables act as antennas.
When laying HF cables (for example, shielded motor cables) 
or suppressed cables (for example, input supply cables, 
control circuit and signal cables) in parallel, a minimum 
clearance of 11.81 in (300 mm) should be ensured in order to 
prevent the radiation of electromagnetic energy. Separate 
cable routing should also be ensured when large voltage 
potential differences are involved. Any necessary crossed 
cabling between the control signal and power cables should 
always be implemented at right angles (90 degrees).
Never lay control or signal cables in the same duct as power 
cables. Analog signal cables (measured, reference and 
correction values) must be shielded.
Earthing
The ground connection (PE) in the cabinet should be 
connected from the input supply to a central earth point 
(mounting plate). All protective conductors should be routed 
in star formation from this earth point and all conductive 
components of the PDS (frequency inverter, motor reactor, 
motor filter, main choke) are to be connected.
Avoid ground loops when installing multiple frequency 
inverters in one cabinet. Make sure that all metallic devices 
that are to be grounded have a broad area connection with 
the mounting plate.
Screen Earth Kit
Cables that are not shielded work like antennas (sending, 
receiving). Make sure that any cables that may carry 
disruptive signals (for example, motor cables) and sensitive 
cables (analog signal and measurement values) are shielded 
apart from one another with EMC-compatible connections.
The effectiveness of the cable shield depends on a good 
shield connection and a low shield impedance.
Use only shields with tinned or nickel-plated copper braiding. 
Braided steel shields are unsuitable.
Control and signal lines (analog, digital) should always be 
grounded on one end, in the immediate vicinity of the supply 
voltage source (PES).