Appendix A
42 H-Max Series Adjustable Frequency Drive    MN04008005E—September 2011    
Relay Board 1 
Relay Board 2 
Notes
Relay board with two change-over contact (SPDT) relays and one relay with normally-open (NO or SPST) contact. 
5.5 mm isolation between channels.
If 230 Vac is used as control voltage from the output relays, the control circuitry must be powered with a separate 
isolation transformer to limit short circuit current and overvoltage spikes. This is to prevent welding on the relay 
contacts. Refer to standard EN60204-1, section 7.2.9.
Relay board with two change-over contact (SPDT) relays and a PTC thermistor input. 5.5 mm isolation between 
channels.
Terminal Signal Description
21 Relay output 1 
Switching capacity 24 Vdc/8A
250 Vac/8A
125 Vdc/0.4A
Minimum switching load 5V/10 mA
22
23
24 Relay output 2 
Switching capacity 24 Vdc/8A
250 Vac/8A
125 Vdc/0.4A
Minimum switching load 5V/10 mA
25
26
32 Relay output 3 
Switching capacity 24 Vdc/8A
250 Vac/8A
125 Vdc/0.4A
Minimum switching load 5V/10 mA
33
Terminal Signal Description
21 Relay output 1 
Switching capacity 24 Vdc/8A
250 Vac/8A
125 Vdc/0.4A
Minimum switching load 5V/10 mA
22
23
24 Relay output 2 
Switching capacity 24 Vdc/8A
250 Vac/8A
125 Vdc/0.4A
Minimum switching load 5V/10 mA
25
26
28 Thermistor input Rtrip = 4.7 kohms (PTC), measuring voltage 3.5V
29