Effective 10/02
Page 4-12Page 4-12
For more information visit: www.cutler-hammer.eaton.comIL17562BH04
Selected
Value
Line
No.
17
18
19
20
21
22
1
2
3
4
5
Display
REMT ON
or
REMT OFF
DIFT ON
or
DIFT OFF
INCT ON
or
INCT OFF
TRNT ON
or
TRNT OFF
ZSWT ON
or
ZSWT OFF
TBYP ON
or
TBYP OFF
LSPU XXX
LSDO XXX
LSDL XX
Choose:
GF A ON
GF T ON
or
GF OFF
Choose:
I2T A ON
I2T T ON
or
I2T OFF
Help Message
ENABLE REMOTE TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
ENABLE DIFFERENTIAL TRIP TO ACTI-
VATE ALARM RELAY OUTPUT OR
DISABLE
ENABLE INCOM TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
ENABLE TRANSITION TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
ENABLE ZERO SPEED SWITCH TRIP TO
ACTIVATE ALARM RELAY OUTPUT OR
DISABLE
ENABLE TRIP BYPASS TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
LOAD SHED PICK-UP CURRENT AS %
OF FLA
LOAD SHED DROP-OUT CURRENT AS
% OF FLA
LOAD SHED DELAY IN SECONDS
ENABLE GROUND FAULT ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
ENABLE I2T ALARM OR TRIP TO
ACTIVATE AUX1 RELAY OUTPUT
OR DISABLE
Setting
Range/ Value
Selection
Toggles between
REMT ON and
REMT OFF
Toggles between
DIFT ON and
DIFT OFF
Toggles between
INCT ON and
INCT OFF
Toggles between
TRNT ON and
TRNT OFF
Toggles between
ZSWT ON and
ZSWT OFF
Toggles between
TBYP ON and
TBYP OFF
50-150%, OFF
(1% increments)
Note: P9L1 and
P9L2 are forced to
be coherent. See
Section 5 explana-
tion.
50-LSPU Value %,
OFF (1% incre-
ments)
Note: P9L1 and
P9L2 are forced to
be coherent. See
Section 5 explana-
tion.
0-5 sec. (0.1 sec.
increments)
If LSPU and LSDO
are both set to
OFF then the SP
AUX1 functions
below are available
and visible:
Toggles between
GF A ON, GF T
ON, and GF OFF
Toggles between
I2T A ON, I2T T
ON, and I2T OFF
Value
as
shipped
REMT
OFF
DIFT OFF
INCT
OFF
TRNT OFF
ZSWT
OFF
TBYP OFF
OFF
OFF
1
GF OFF
I2T T ON
Section
Reference
5.8
5.8
5.8
5.8
5.8
5.8
5.9.1
5.9.2
5.9.3
5.9.4
5.9.4
Page 9 SP AUX1 SETTINGS FOR AUX2 RELAY OUTPUT CONFIGURATION