Effective 10/02
Page 4-6Page 4-6
For more information visit: www.cutler-hammer.eaton.comIL17562BH04
Table 4.3 View Settings Mode/Program Worksheet
Program Date Control Schematic
Unit ID/Starter Type Work Order #
Motor HP Mfgr. Serial# Volts
FLA LRC Stall Time/LRT Accel Time
SF RTD Type Other
Selected
Value
Line
No.
1
2
3
4
5
6
7
8
9
1
2
3
4
5
Display
FLA XXXX
LRC XXXX
LRT XXX
UTC XXX
PCT XXXX
GCT XXXX
FREQ 50
or
FREQ 60
REV
or
NON REV
STOP XX
RTD IN C
or
RTD IN F
WD T XXX
WD A XXX
MB T XXX
MB A XXX
Help Message
FULL LOAD AMPS
LOCKED ROTOR CURRENT % OF FLA
MAXIMUM ALLOWABLE STALL TIME IN
SECONDS
ULTIMATE TRIP CURRENT IN % FLA
PHASE CT RATIO NUMERATOR IN
PRIMARY AMP
GROUND CT RATIO NUMERATOR IN
PRIMARY AMP
50 OR 60 HERTZ LINE FREQUENCY
REVERSING OR NONREVERSING
STARTER
MOTOR STOP CURRENT LEVEL IN %
OF PHASE CT RATIO NUMERATOR
DISPLAYED IN DEGREES C OR F
WINDING TEMP TRIP
WINDING TEMP ALARM
MOTOR BEARING TRIP
MOTOR BEARING ALARM
Setting
Range/ Value
Selection
10-3000 amps (1
amp. increments)
300-1200 % (1 %
increments)
1-120 sec. (1 sec.
increments)
85-150% (1%
increments)
10-4000 A (incre-
ments of 1)
10-4000 A (incre-
ments of 1)
Toggles between
FREQ 50 and
FREQ 60
Toggles between
REV and NONREV
2-20% of phase CT
ratio numerator
(1% increments)
Toggles between
RTD IN C and RTD
IN F
0-199°C, OFF / 32-
390°F, OFF
(1°increments)
0-199°C, OFF / 32-
390°F, OFF
(1°increments)
0-199°C, OFF / 32-
390°F, OFF
(1°increments)
0-199°C, OFF / 32-
390°F, OFF
(1°increments)
Value
as
shipped
10
300
1
85
10
50
FREQ 60
NONREV
5%
RTD IN C
100
80
100
80
Section
Reference
5.1.1
5.1.2
5.1.3
5.1.4
5.1.5
5.1.6
5.1.7
5.1.8
5.1.9
5.2.1
5.2.2
5.2.3
5.2.4
5.2.5
Page 1 SP MOTOR SP MOTOR SETTINGS FOR MOTOR CONSTANTS
Page 2 SP RTD SETTINGS FOR RTD INPUTS