Effective 10/02
Page 4-7
For more information visit: www.cutler-hammer.eaton.com
Page 4-7
IL17562BH04
Selected
Value
Section
Reference
5.2.6
5.2.7
5.2.8
5.2.9
5.2.10
5.3.1
5.3.2
5.3.3
5.3.4
5.3.5
5.3.6
5.3.7
5.3.8
5.3.9
5.3.10
5.3.11
5.3.12
5.3.13
5.3.14
Value
as
shipped
80
80
100
80
DIAG ON
24%
5
2
OFF
3
1000%
60
2
OFF
60
10
OFF
10
2
Help Message
LOAD BEARING TRIP
LOAD BEARING ALARM
AUXILIARY TRIP
AUXILIARY ALARM
ALARM ON RTD FAILURE DIAGNOSTIC
GROUND FAULT TRIP LEVEL IN % OF
GROUND CT RATIO NUMERATOR
GROUND FAULT START DELAY IN
CYCLES
GROUND FAULT RUN DELAY IN CYCLES
INSTANTANEOUS OVERCURRENT
IN % FLA
INSTANTANEOUS OVERCURRENT
START DELAY IN CYCLES
JAM TRIP LEVEL IN % FLA
JAM TRIP AND ALARM START DELAY
IN SECONDS
JAM TRIP RUN DELAY IN SECONDS
UNDERLOAD TRIP LEVEL IN % FLA
UNDERLOAD TRIP AND ALARM START
DELAY IN SECONDS
UNDERLOAD TRIP RUN DELAY
IN SECONDS
PHASE UNBALANCE TRIP LEVEL
PHASE UNBALANCE TRIP AND ALARM
START DELAY IN SECONDS
PHASE UNBALANCE TRIP RUN DELAY
IN SECONDS
Line
No.
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Display
LB T XXX
LB A XXX
AX T XXX
AX A XXX
DIAG ON
or
DIAG OFF
GFT XXX
GFSD XX
GFRD XX
IOC XXXX
IOCSD XX
JMT XXXX
JMSD XXX
JMTR XXX
ULT XXX
ULSD XXX
ULTR XXX
UBT XXX
UBSD XXX
UBTR XXX
Setting
Range/ Value
Selection
0-199°C, OFF / 32-
390°F, OFF
(1°increments)
0-199°C, OFF / 32-
390°F, OFF
(1°increments)
0-199°C, OFF /
32-390°F, OFF
(1°increments)
0-199°C, OFF /
32-390°F, OFF
(1°increments)
Toggles between
DIAG ON and
DIAG OFF
2-55% of Ground
Ct ratio numerator,
OFF
(1% increments)
2-60 ac cycles (1
cycle increments)
0-60 ac cycles (1
cycle increments)
300-1600%, OFF
(1% increments)
2-60 ac cycles (1
cycle increments)
100-1200%, OFF
(1% increments)
0-1200 sec. (1
sec. increments)
0-240 sec. (1 sec.
increments)
6-90%, OFF (1%
increments)
0-120 sec. (1 sec.
increments)
0-240 sec. (1 sec.
increments)
4-40%, OFF (1%
increments)
0-120 sec. (1 sec.
increments)
0-240 sec. (1 sec.
increments)
Page 3 SP TRIP SETTINGS FOR TRIP EVENTS