Page 3-2
www.eaton.com
IB02602002E MP-4000
Alarm Setting Range
Ground Fault: Off, 2% to 55% CT Ratio
Overload I
2
t: Off, 60 to 99% I
2
t
Jam: Off, 100 to 1,200% FLA
Underload: Off, 6 to 90% FLA
Phase Unbalance: Off, 4 to 40% I
2
/I
1
Run Delay Timers: Off, 0 to 240 sec.
Phase Unbalance Alarm Threshold Off, 1 to 100 V
Phase Unbalance Alarm Run Delay Off, 1 to 1,200 sec.
Underfrequency Alarm Threshold Off, 15 to 60 Hz
Under frequency Alarm run Delay Off, 0 to 60 sec.
Voltage Unbalance Alarm Off, 0 to 480 sec.
Overfrequency Alarm Threshold Off, 15 to 70 Hz
Overfrequency Alarm Run Delay 0 to 60 sec.
Overvoltage Main Alarm Threshold Off, 10 to 150 V
Overvoltage Main Alarm Run Delay Off, 0 to 480 sec.
Main UV Alarm Run Delay Off, 0 to 60 sec.
Under Power Alarm Threshold Off, 0.06 to .90 *FLA *VT
Underpower Alarm Run Delay Off, 0 to 480 sec.
Leading Power Factor Alarm Threshold 1 Off, 0.05 to 0.99
Lagging Power Factor Alarm Threshold 2 Off, 0.05 to 0.99
Power Factor Alarm Start Delay Off, 0 to 60 sec.
Power Factor Alarm Run Delay Off, 0 to 60 sec.
Start Control Functions
Starts per Time: 1 to 10 starts
Time for Starts per Time: Off, 1 to 240 min.
Time Between Starts: Off, 1 to 240 min.
Number of Cold Starts: 1 to 5 starts
Motor Transition Current: 10 to 300% FLA
Time for Transition: 0 to 1,200 sec.
Incomplete Sequence Timer: Off, 1 to 240 sec.
Long Acceleration Timer: Off, 1 to 1,200 sec.
Antibackspin Timer: Off, 1 to 3,600 sec.
RTD Inputs (Requires URTD module)
Sensor Types: 10 ohm copper
100 ohm nickel
120 ohm nickel
100 ohm platinum
URTD Module Communications
Interface: Plastic optical ber
(preferred)
Electrical (3-wire)
Fiber Optic Cable: Type HFBR-ELS (length) -
precut low-loss with
connectors
Type HBFR-EUS (length) -
bulk low-loss without
connectors
Type HBFR-RLS (length) -
standard-loss, acceptable
for <10m (<32.8 ft)
Clock
Accuracy: Freerunning ± 1 min./mo.
@ 25°C (77°F). Automati-
cally updated by PowerNet
host.
IPONI Communications (Section 10 contains more protocols.)
Type: 2-wire, 115.2 kHz carrier
Baud Rate: 1,200 ASK or 9,600 FSK
Max. Distance: 10,000 ft (3048 m)
Protocol: INCOM
Functions: Read/write setpoints
Read metered values
Read trip/alarms
Read events
Read history
Reset history
Reset functions
Emergency override
Trip
View starting prole
Logging
Log Book: 100 events
Log Event: 20 trips and alarms
Log Start: Last 4 starts
Start Prole: Last 4 starts (communications
port only)
History Records: Motor, trips, alarms, and totals
Environmental Ratings
Operating Temp.: -20 to + 60°C (-4 to +140°F)
Storage Temp.: -45 to + 85°C (-49 to +185°F)
Humidity: 0 to 95% non-condensing
Dimensions (Fixed Mount Case Only)
Height: 10.25 in. (260.4 mm)
Width: 6.72 in. (170.7 mm)
Depth: 4.3 in. (109.2 mm)
Weight: 5 lbs. (2.3 kg)
8.0 lbs. (3.6 kg) (with URTD
and PONI)
Standards
ANSI/IEEE C37.90-1989
Standard for Relay Systems Associated with Electric Power Apparatus.
ANSI/IEEE C37.90.1-1989
Standard Surge Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems
ANSI/IEEE C37.90.2-1995
Standard Withstand Capability of Relay Systems to Radiated
Electromagnetic Interference from Transceivers
UL-1053
Ground Fault Sensing and Relaying Equipment
Emissions (EN-50081-2)
EN 50011 CISPR-11, Class A, CFR 47 FCC Part 15
Subpart b Class A
EN-61000-6-2 Immunity
EN 61000-4-2 ESD
EN 61000-4-3 RF Radiated Immunity
EN 61000-4-4 EFT/Burst Immunity
EN 61000-4-5 Surge Immunity
EN 61000-4-6 RF Conducted Immunity
EN 61000-4-8 Power Frequency Magnetic Field Immunity
EN 61000-4-11 Voltage Variation Immunity