EasyManua.ls Logo

Eaton MP-4000 - Checking Discrete Input 1; Checking Discrete Input 2; Verify Voltage Inputs

Eaton MP-4000
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 11-2
www.eaton.com
IB02602002E MP-4000
11.10 Checking Discrete Input 1
Use P13L7 to determine if discrete input 1 is on or off. Apply or re-
move 120 Vac to check both states.
11.11 Checking Discrete Input 2
Use P13L8 to determine if discrete input 2 is on or off. Apply or re-
move 120 Vac to check both states.
11.12 Verify Voltage Inputs
A DVM can be used to verify readings displayed by the MP-4000.
Measure voltage between the ground input connection and each
voltage input. Allow tolerance for errors in the DVM and the PTs of
the motor starter.