www.eaton.com Page 5-15
MP-4000 IB02602002E
5.24.5 Setting P24L5
P24L5 enables the Under Frequency Alarm or Trip to activate the AUX
2 Relay Output. This function can be disabled by setting this setpoint
to “OFF”.
5.24.6 Setting P24L6
P24L6 enables the Underpower Alarm or Trip to activate the AUX 2
Relay Output. This function can be disabled by setting this setpoint to
“OFF”.
5.24.7 Setting P24L7
P24L7 enables the Power Factor Alarm or Trip to activate the AUX 2
Relay Output. This function can be disabled by setting this setpoint to
“OFF”.
5.25 Page 25, SP2 SYS, P25L1 to L9, WATT Hours
Display
5.25.1 Setting P25L1, Watt Hours Display
P25L1 sets the watt hours display to kilo, mega, or giga.
5.25.2 Setting P25L2, Volt-amps Reactive Display
P25L2 sets the volt-amps reactive display to kilo, mega, or giga.
5.25.3 Setting P25L3, Volt-amps Display
P25L3 sets the volt-amps display to kilo, mega, or giga.
5.25.4 Setting P25L4, 3-Phase Watts Display
P25L4 sets the 3-phase watts display to kilo or mega.
5.25.5 Setting P25L5, 3-Phase Volt-amp Reactive Display
P25L5 sets the 3-phase volt-amps reactive display to kilo or mega.
5.25.6 Setting P25L6, 3-Phase Volt-amp Display
P25L6 sets the 3-phase volt-amps display to kilo or mega.
5.25.7 Setting P25L7, External PT Ratio
P25L7 sets the external PT Ratio display to a value from 1-250:1. The
external PT should step the voltage down to 120 Vac nominal at the
voltage inputs of the MP-4000.
5.25.8 SettingP25L8,PTConguration
P25L8 selects between WYE (0), delta (1), or open delta (2).
5.25.9 Setting P25L9, Voltage Display
P25L9 sets the voltage display to volts or kilovolts.
5.26 Page 26, SP COMM Settings for RS232
Communications
P26L1 enables (on) or disables (off) the RS-232 communications
mode. Note that URTD and PONI communications are disabled when
the MP-4000 is in the RS-232 mode.