Page 6-12
www.eaton.com
IB02602002E
MP-4000
Figure 6.12 Wiring to URTD Module.
3
2
1
2
1
3
NOTES:
1. CONNECT CABLE SHIELD AT RTD MODULE TERMINALS ONLY..
CUT SHIELD SHORT AT MOTOR END AND USE SHRINK TUBING
OR ELECTRICAL TAPE TO INSULATE..
2. RTD
CONNECTIONS BETWEEN INDIVIDUAL RTD' s SHOULD BE MADE AT
THE MOTOR OR THE MP - 4000
..
3. TERMINAL 16 OR 32 ON THE RTD MODULE SHOULD BE CONNECTED
TO AN EARTH GROUND..
UNIVERSAL RTD
MODULE TERMINALS
CABLE
SHIELD
RTD TERMINALS
CABLE SHIELD WIRE
RTD WIRING (THREE-LEAD TYPE)
RTD WIRING (TWO-LEAD TYPE)
s MUST BE NOT BE GROUNDED AT THE MOTOR, AND NO COMMON