96
Chapter 6 - Pump control application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021   www.eaton.com
Table 38.  Multi-pump status (Cont.).
M7.2 - Multi-pump status (*DM1 Pro).
M7. 2.1
Drive 1
ID 2219
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
5
Options:
0 = Stopped;
1 = Sleep;
2 = Regulating;
3 = Wait for CMD
4 = Following; or
5 = Unknown.
Description:
Provides the run status of drive 1 while using the multi-pump mode.
M7.2.2
Drive 2
ID 2231
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
5
Options:
0 = Stopped;
1 = Sleep;
2 = Regulating;
3 = Wait for CMD
4 = Following; or
5 = Unknown.
Description:
Provides the run status of drive 2 while using the multi-pump mode.
M7. 2. 3
Drive 3
ID 2243
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
5
Options:
0 = Stopped;
1 = Sleep;
2 = Regulating;
3 = Wait for CMD
4 = Following; or
5 = Unknown.
Description:
Provides the run status of drive 3 while using the multi-pump mode.
M7.2.4
Drive 4
ID 2255
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
5
Options:
0 = Stopped;
1 = Sleep;
2 = Regulating;
3 = Wait for CMD
4 = Following; or
5 = Unknown.
Description:
Provides the run status of drive 4 while using the multi-pump mode.
M7. 2. 5
Drive 5
ID 2267
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
5
Options:
0 = Stopped;
1 = Sleep;
2 = Regulating;
3 = Wait for CMD
4 = Following; or
5 = Unknown.
Description:
Provides the run status of drive 5 while using the multi-pump mode.
M7.3 - Network status (*DM1 Pro).
M7.3.1
Drive 1
ID 2220
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Disconnected;
1 = Fault;
2 = Pump lost;
3 = Need alternation; or
4 = No error.
Description:
Provides the network status of drive 1 while using the multi-pump mode.