17
Instruction Leaet PUB53675
Effective December 2021
PowerXL DM1 and DM1 Pro series VFD
EATON www.eaton.com
Table 6. International cable and fuse sizes. 
IEC Cable and Fuse Sizes
Output rating Input rating IEC application
Input voltage
Frame size
Catalog number
CT/IH
current amps
VT/IL
current amps
CT/IH
current amps
VT/IL
current amps
Recommended fuse
rating 100 kAIC
Maximum allowed
use rating 100 kAIC
Recommended
circuit breaker
rating 100 kAIC
(open type only for
3 phase)
Maximum allowed
circuit breaker
rating 100 kAIC
(open type only for
3 phase)
Maximum allowed
miniature circuit
breaker rating 10/14
kAIC
Recommended Type
E CMC rating 65
kAIC
IEC cable size line
and motor mm
2
IEC cable size
ground mm
2
Terminal size line
and motor mm
2
Terminal size ground
mm
2
100 Vac
to
120 Vac
50/60
Hz
1 phase
FR1 DM1-111D6 1.6 2.5 6.4 9.6 15 30 15 30 30 \ 2.5 2.5 0.2-6 TBD
DM1-113D0 3 4.8 12 20 30 70 30 70 63 \ 6 6 0.2-6 TBD
FR2 DM1-114D8 4.8 6.9 20 29 40 90 40 90 63 \ 10 10 0.5-16 TBD
DM1-116D9… 6.9 7.8 29 34.3 45 125 45 125 63 \ 10 10 0.5-16 TBD
200 Vac
to
240 Vac
50/60
Hz
1 phase
FR1 DM1-121D6 1.6 2.5 3.2 5 10 15 15 15 15 \ 2.5 2.5 0.2-6 TBD
DM1-123D0 3 4.8 6 9.6 20 30 20 30 30 \ 2.5 2.5 0.2-6 TBD
DM1-124D8… 4.8 7.8 10 16 30 60 30 60 63 \ 4 4 0.2-6 TBD
FR2 DM1-127D8… 7.8 11 16 23 35 80 35 80 63 \ 6 6 0.5-16 TBD
DM1-12011… 11 17.5 23 35 60 125 60 125 63 \ 10 10 0.5-16 TBD
FR3 D M1-12 0 17… 17.5 25.3 39.6 49.6 80 200 80 200 \ \ 16 16 0.5-16 TBD
200 Vac
to
240 Vac
50/60
Hz
3 phase
FR1 DM1-321D6… 1.6 2.5 2.1 3.3 6 6 15 15 5 6.3 2.5 2.5 0.2-6 1.5-6.0
DM1-
323D0…
3 4.8 3.9 5.8 10 15 15 15 10 6.3 2.5 2.5 0.2-6 1.5-6.0
DM1-
324D8…
4.8 7.8 5.8 9.4 15 20 15 15 15 10 2.5 2.5 0.2-6 1.5-6.0
DM1-
327D8…
7.8 11 9.4 13.2 20 30 20 20 20 16 4 4 0.2-6 1.5-6.0
FR2 DM1-32011 11 17.5 12.7 20.1 35 40 30 30 30 25 6 6 0.5-16 4.0-10
DM1-32017 17.5 25.3 20.1 29.1 45 60 45 45 40 32 10 10 0.5-16 4.0-10
FR3 DM1-32025… 25.3 32.2 29.1 37 60 70 50 50 50 40 10 10 0.5-16 6.0-10
FR4 DM1-32032… 32.2 48.3 35.4 53.1 80 100 80 80 \ \ 25 16 0.5-35 10-16
DM1-
32048…
48.3 62.1 5 3.1 68.3 110 125 100 100 \ \ 35 16 0.5-35 10-16
380 Vac
to
480 Vac
50/60
Hz
3 phase
FR1 DM1-341D5 1.5 2.2 1.8 2.6 6 6 15 15 4 6.3 2.5 2.5 0.2-6 1.5-6.0
DM1-
342D2…
2.2 4.3 2.6 5.2 10 10 15 15 8 6.3 2.5 2.5 0.2-6 1.5-6.0
DM1-
344D3…
4.3 5.6 5.2 6.7 15 15 15 15 10 10 2.5 2.5 0.2-6 1.5-6.0
DM1-
345D6
5.6 7.6 6.7 9.1 15 30 15 15 15 10 2.5 2.5 0.2-6 1.5-6.0
FR2 DM1-
347D6…
7.6 12 9.1 14.4 25 30 20 20 20 16 4 4 0.5-16 4.0-10
DM1-34012… 12 16 14.4 19.2 30 40 30 30 25 25 6 6 0.5-16 4.0-10
DM1-34016 16 23 19.2 27.6 45 60 40 40 32 32 10 10 0.5-16 4.0-10
FR3 DM1-34023.. 23 31 26.5 35.7 60 70 50 50 \ 40 10 10 0.5-16 6.0-10
FR4 DM1-34 031… 31 38 35.7 43.7 70 70 70 70 \ 50 16 16 0.5-35 10-16
DM1-
34038…
38 46 43.7 52.9 80 80 80 80 \ 58 25 16 0.5-35 10-16
525 Vac
to
600 Vac
50/60
Hz
3 phase
FR2 DM1-
354D5…
4.5 7.5 6 9 15 30 \ \ \ 10 2.5 2.5 0.5-16 2.5-10
DM1-
357D5…
7.5 10 9 12 20 40 \ \ \ 16 2.5 2.5 0.5-16 2.5-10
DM1-35010… 10 13.5 12 16.2 25 50 \ \ \ 25 6 6 0.5-16 4-10
FR3 DM1-35013… 13.5 18 16.2 21.6 35 70 \ \ \ 25 6 6 0.5-16 6-10
FR4 DM1-35018… 18 22 21.6 26.4 40 80 \ \ \ 32 10 10 0.5-35 10-16
DM1-35022… 22 27 26.4 32.4 50 100 \ \ \ 40 10 10 0.5-35 10-16
Notes:
Line and motor cable size is selected according to IEC 60364-5-52:2009 Table B.52.4 for copper conductor with PVC insulation with a wiring condition of ambient temperature
30°C in air and an installation method of “B2” (cables in conduit and cable trunking systems). For other wiring conditions, please refer to the standard of IEC 60364-5-52:2009
for suitable cable sizes.
Earthing conductor size is determined by the cross-sectional area of phase conductors according to IEC/EN 61800-5-1:2007 Table 5. So if phase conductor size is changed,
earthing conductor size should also be changed accordingly.
If power cubes or bypass are used, a Class gG/gL fuse is recommended.