16
Instruction Leaet PUB53675
Effective December 2021
PowerXL DM1 and DM1 Pro series VFD
EATON www.eaton.com
Cable and fuse guidelines
Table 5. North America cable and fuse sizes. 
UL cable and fuse sizes
Output
rating
Input
rating
UL application
Input voltage
Frame size
Drive catalog
number
CT/IH
current amps
VT/IL
current amps
CT/IH
current amps
VT/IL
current amps
Recommended fuse
rating (Class J, T, CF
or CC) 100 kAIC
Maximum allowed
fuse rating (Class
J, T, CF or CC) 100
kAIC
Recommended
inverse-time molded-
case circuit breaker
rating 100 kAIC
(open type only for 3
phase)
Maximum allowed
inverse-time molded-
case circuit breaker
rating 100 kAIC
(open type only for 3
phase)
Maximum allowed
miniature circuit
breaker rating 10/14
kAIC
Recommended Type
E CMC rating 65
kAIC
NEC wire size
line and motor
AWG
NEC wire size
ground
AWG
Terminal size
line and motor
AWG
Terminal size
ground
AWG
100 Vac
to
120 Vac
50/60
Hz
1 phase
FR1 DM1-111D6… 1.6 2.5 6.4 9.6 15 30 15 30 30 \ 14 10 18-8 16-8
DM1-113D0… 3 4.8 12 20 30 70 30 70 63 \ 10 8 18-8 16-8
FR2 DM1-114D8… 4.8 6.9 20 29 40 90 40 90 63 \ 8 8 20-6 12-6
DM1-116D9… 6.9 7.8 29 34.3 45 125 45 125 63 \ 8 6 20-6 12-6
200 Vac
to
240 Vac
50/60
Hz
1 phase
FR1 DM1-121D6… 1.6 2.5 3.2 5 10 15 15 15 15 \ 14 14 18-8 16-8
DM1-123D0… 3 4.8 6 9.6 20 30 20 30 30 \ 14 10 18-8 16-8
DM1-124D8… 4.8 7.8 10 16 30 60 30 60 63 \ 10 8 18-8 16-8
FR2 DM1-127D8… 7.8 11 16 23 35 80 35 80 63 \ 10 8 20-6 12-6
DM1-12011… 11 17.5 23 35 60 125 60 125 63 \ 8 6 20-6 12-6
FR3 DM1-12 017… 17.5 25.3 39.6 49.6 80 200 80 200 \ \ 6 6 20-6 8-6
200 Vac
to
240 Vac
50/60
Hz
3 phase
FR1 DM1-321D6… 1.6 2.5 2.1 3.3 6 6 15 15 5 6.3 14 14 18-8 16-10
DM1-323D0… 3 4.8 3.9 5.8 10 15 15 15 10 6.3 14 14 18-8 16-10
DM1-324D8… 4.8 7.8 5.8 9.4 15 20 15 15 15 10 14 12 18-8 16-10
DM1-327D8… 7.8 11 9.4 13.2 20 30 20 20 20 16 12 10 18-8 16-10
FR2 DM1-32011… 11 17.5 12.7 20.1 35 40 30 30 30 25 10 10 20-6 12-8
DM1-32017… 17.5 25.3 20.1 29.1 45 60 45 45 40 32 8 10 20-6 12-8
FR3 DM1-32025… 25.3 32.2 29.1 37 60 70 50 50 50 40 8 8 20-6 10-8
FR4 DM1-32032… 32.2 48.3 35.4 53.1 80 100 80 80 \ \ 4 8 20-2 8-6
DM1-32048… 48.3 62.1 53.1 68.3 110 125 100 100 \ \ 3 6 20-2 8-6
380 Vac
to
480 Vac
50/60
Hz
3 phase
FR1 DM1-341D5… 1.5 2.2 1.8 2.6 6 6 15 15 4 6.3 14 14 18-8 16-10
DM1-342D2… 2.2 4.3 2.6 5.2 10 10 15 15 8 6.3 14 14 18-8 16-10
DM1-344D3… 4.3 5.6 5.2 6.7 15 15 15 15 10 10 14 14 18-8 16-10
DM1-345D6… 5.6 7.6 6.7 9.1 15 30 15 15 15 10 14 10 18-8 16-10
FR2 DM1-347D6… 7.6 12 9.1 14.4 25 30 20 20 20 16 12 10 20-6 12-8
DM1-34012… 12 16 14.4 19.2 30 40 30 30 25 25 10 10 20-6 12-8
DM1-34016… 16 23 19.2 27.6 45 60 40 40 32 32 8 10 20-6 12-8
FR3 DM1-34023.. 23 31 26.5 35.7 60 70 50 50 \ 40 8 8 20-6 10-8
FR4 DM1-340 31… 31 38 35.7 43.7 70 70 70 70 \ 50 6 8 20-2 8-6
DM1-34038… 38 46 43.7 52.9 80 80 80 80 \ 58 4 8 20-2 8-6
525 Vac
to
600 Vac
50/60
Hz
3 phase
FR2 DM1-354D5… 4.5 7.5 6 9 15 30 \ \ \ 10 14 10 20-6 12-8
DM1-357D5… 7.5 10 9 12 20 40 \ \ \ 16 14 10 20-6 12-8
DM1-35010… 10 13.5 12 16.2 25 50 \ \ \ 25 10 10 20-6 12-8
FR3 DM1-35013… 13.5 18 16.2 21.6 35 70 \ \ \ 25 10 8 20-6 10-8
FR4 DM1-35018… 18 22 21.6 26.4 40 80 \ \ \ 32 8 8 20-2 8-6
DM1-35022… 22 27 26.4 32.4 50 100 \ \ \ 40 8 8 20-2 8-6
Notes:
 Line and motor cable size is selected according to UL 508C Table 40.3 for copper conductor rated 75°C. Use only with copper wire rated 75°C here. Size requirements for
other different wire types are defined in the National Electrical Code
®
, ANSI/NFPA
®
70.
 Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 508C Table 6.4.
 If power cubes or bypass are used, a UL listed Class RK5, J, T or equivalent fuse is recommended.