EasyManua.ls Logo

Eaton PXR10 - Page 101

Eaton PXR10
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.1 EtherNet/IP
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com 97
17 Settings - instan-
taneous short-
circuit release (I
i
)
R/W Unsigned Settings - instantaneous short-circuit release
(I
i
= n x I
n
)
NZM PXR20: R
NZM PXR25: R/W
NZM PXR20:
20: 2
30: 3
40: 4
50: 5
60: 6
70: 7
80: 8
90: 9
100: 10
110: 11
120: 12
140: 14
160: 16
180: 18
The following applies to the NZM PXR25:
The value range [20 - 180] corresponds to 2 to 18,
in increments of 0.1 (1 for values)
A
18
0 0x0001 Type of ground-
fault detection
R Unsigned Type of ground-fault detection:
0: differential current detection
19
0 - 1 0x0003 Settings - functio-
ning of the
ground-fault
protection
R/W Encoded Type of ground-fault protection 0: trip
1: alarm
2: OFF
20
0 0x0001 ground-fault
release - wave-
form
R/W Encoded ground-fault release - waveform:
0: flat
1: I
2
t
21 Settings - ground-
fault release (I
g
)
R/W Unsigned Settings - ground-fault release (I
g
= n x I
n
)
NZM PXR20: R
NZM PXR25: R/W
NZM PXR20:
20: 0.2
30: 0.3
40: 0.4
60: 0.6
80: 0.8
100: 1.0
The following applies to the NZM PXR25:
The value range [20 - 100] corresponds to 0.2 to
1.0, in increments of 0.1 (10 for values)
A
Instance
Bit
field
Mask
field
Setpoint name R/W Format Description or value Unit

Table of Contents

Related product manuals