10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.1 EtherNet/IP
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com 83
10.1.2 IP configuration/DIP Switch Settings
The DIP switches are used to configure the device’s fieldbus addresses.
Flipping a single switch adds the switch specific value to the total address
value. As a result, values in a range from 0 to 255 can be configured that
way.
Table 45: Fieldbus address configuration via DIP switch
For example, flipping switches 4 and 6 results in the address 40.
Figure 20: DIP switches flipping example
The valid settings for EtherNet/IP are shown on table 46.
Table 46: Fieldbus address configuration via DIP switch
Switch 12345678
Value 1248163264128
Switches
Setting Value
Remarks
000 If the DIP switches are set to 0, the IP address settings stored in the NV-memory of the
device are used.
The factory default behaviour is DHCP.
The IP address settings can be configured by the IPconfig tool.
The tool can be downloaded here:
https://www.eaton.com/digitalnzm
001 If the DIP switches are set to 1, the address settings of the device are as follows:
IP address: 192.168.1.1
Subnet mask: 255.255.255.0
Default Gateway: 192.168.1.2
001 - 254
If the DIP switches are set in the range from 1 to 254, the IP address settings of the device
are determined by the switches:
IP address: 192.168.1.<DIP Switch Setting>
Subnet mask: 255.255.255.0
Default Gateway: 192.168.1.1
255 Invalid Setting. Device will not start-up properly.