EasyManua.ls Logo

Eaton PXR10 - Profinet

Eaton PXR10
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
132 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
10.2.3.11 Exception codes
If there is an error in the request or the response, the release will return an
exception code, via index 2167.
Table 79: Exception codes - EtherCAT
Modbus returned
exception code
values
Meaning
0 No error
8 Timeout error occurred
10 Illegal function exception
11
Illegal data address
12
Illegal data value
13 Slave device failure
14 Slave acknowledge
15 Slave device busy
16 Memory parity error
17 ECAM path unavailable
18 ECAM target device failed to respond

Table of Contents

Related product manuals