9 Modbus RTU – integrated Modbus port specification
9.3 Modbus register map
76 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
9.3.10 Primary status codes
Table 37: Primary status codes
9.3.11 Secondary status codes
Table 38: Secondary status codes
9.3.12 Reason codes
Table 39: Reason codes
Code Meaning
0x01 open
0x02 closed
0x03 tripped
0x04 Alarm active
0x0D Threshold value active
Code Meaning
0x01 not applicable
0x03 Test mode
0x07 has been switched on since last trip / triggered alarm
0x08 alarm
Code Meaning
0x0000 unknown
0x0001 normal
0x0003 Instantaneous short circuit
0x000E Auxiliary power supply too low
0x0011 Current imbalance
0x0021 Control via the communication interface
0x0025 Coil monitoring
0x002B Diagnostic warning #2 (configuration read error)
0x003D Overload
0x003E Short-time delay
0x0049 Phase currents are close to the threshold value, load alarm
0x004C Override
0x004D Setpoint error
0x004E Overtemperature
0x0050 Overload (neutral conductor)
0x0054 Ground fault
0x0071 Calibration