10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.1 EtherNet/IP
104 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Table 56: Remote control - EtherNet/IP
10.1.4.6 Date and time
The release supports the reading and writing of real-time clock information
by the Ethernet communication adapter module EtherNet/IP.
Eight registers, starting with instance number 350, are reserved for this
purpose.
Table 57: Real-time clock - EtherNet/IP
Command
group
Definition Bit
Byte 2 Byte 1 Byte 0
Reset Reset the trip 0 0 2
Reset the min./max. values of the L-N voltages
1)
0 1 15
Reset the min./max. values of the L-L voltages
1)
0 1 14
Reset the peak power requirement
1)
0 0 4
Reset all min./max. values 0 1 4
Reset the energy
1)
0 0 8
Reset the power-up display 0 0 3
Maintenance
mode
Activate the maintenance mode 1 0 8
Deactivate the maintenance mode 1 0 9
1) PXR25 only!
Instance Definition Data range
350 Month 01. Dez
351 Day Jan 31
352 Year 2000 - 2099
353 Day of the week 1 = Sunday
7 = Saturday
354 Hour 0 - 23
355 Minute 0 - 59
356 Seconds 0 - 59
357 1/100 of a second 0 - 99