10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
126 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
The following indexes are assigned to the data objects.
Table 70: Event summary - EtherCAT
Table 71: Historical trip / major alarm event - EtherCAT
Index
[Hex]
Format R/W Description
(historical event overview)
213C Encoded R/W Event type: summary = 0x8EFF
213D Unsigned 32 R Earliest event ID
213E Unsigned 32 R Latest event ID
213F
Unsigned 32 R/W Requested event ID
2140 Unsigned 32 R Previous event ID
2141 Unsigned 32 R Next event ID
2142
Date/time R Date/time
2143
Encoded R Data format:
0x0000, 0x0001, 0x0004, 0x0005, 0x0005, 0x0006
2144
B0 R Valid bit of the object
2145 Encoded R Cause of event:
00: boot process - time OK
01: download of the setpoint values
02: time has been adjusted
03: trip
04: alarm
05: test mode has been selected
06: exiting the test mode
08: boot process - no time
09: test completed
10: maintenance mode activated
11: maintenance mode deactivated
12: opened via the communication interface
13: closed via the communication interface
Index
[Hex]
Format R/W Description
(historical event overview)
Unit
213C Encoded R/W Event type:
trip: 0x80FF
alarm: 0x81FF
–
213D Unsigned 32 R Earliest event ID –
213E
Unsigned 32 R Latest event ID –
213F
Unsigned 32 R/W Requested event ID –
2140 Unsigned 32 R Previous event ID –
2141 Unsigned 32 R Next event ID –
2142 Date/time R Date/time –
2143
Encoded R Data format:
trip: 0x0004
main alarm: 0x0005
–
2144
Bit 15 – Bit 0 R Valid bits of the object –
2145 Bit 31 – Bit 16 R Valid bits of the object –
2146 Encoded R Status reason (primary, secondary, reason) –