10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.3 Profinet
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com 139
73 F9 Overload pre-warning 1
81 107 Counter - I
sd
, I
i
tripping 1
82 108 Counter - I
r
, I
g
tripping 1
83 109 Operations counter 1
84 10A Counter - I
sd
tripping 1
85 10B Counter - I
i
tripping 1
86
10C Counter - bypass tripping 1
87 10D Counter - I
r
tripping 1
88
10E Counter - I
g
tripping 1
89
10F Counter - trips total 1
8A 110 Counter - test mode tripping 1
8B 111 Counter - number of openings via the communication
interface
1
8C
112 Counter - external actuation
1)
1
8D 113 Time of last actuation
(year, month, day, hour, minute, second)
–
8E
114 Operating time
2)
in minutes 1
8F 115 Operating time
2)
in hours 1
90 116 Operating time
2)
in days 1
91 117 Residual life
3)
–
1) An external actuation is a switching operation that is not initiated by the trip unit, such as manual
switching, switching via an externally wired remote operator or the actuation of a push-to-trip button.
2) The operating time counter will start as soon as the device is energized, either autonomously or through
an external power supply.
3) 0 points ≙ 100 % residual life
10.000 points ≙ 0 % residual life
Conversion formula: Residual life expressed as a percentage = 100 - (point value / 100)
Index (Hex) Object
IEEE floating
point
Fixed point
(FP)
Description
(Values in brackets reflect the
American notation.)
Scale factor
(FP)