10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.3 Profinet
150 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Table 87: Setting group 2: “Modbus” group - Profinet
Index
[Hex]
Bit
field
Mask
field
Setpoint
name
R/W Format Description or value Unit
2 15 - 0 0xFFFFFF Password W Encoded 0000 (default setting) –
3 15 - 0 0xFFFFFF Group 2 =
on-board
Modbus
R/W Encoded 0x02FF –
4 15 - 0 Integrated
Modbus -
communica-
tion address
R/W Encoded 001 - 247
(default setting 002)
–
5
15 - 0 Integrated
Modbus -
baud rate
R/W Encoded 00: 9,600 bit/s
01: 19,200 bit/s (default setting)
02: 38,400 bit/s
02: 57,600 bit/s
–
6
15 - 0 Integrated
Modbus -
parity
R/W Encoded 00: none
01: odd
02: even (default setting)
–
7 15 - 0 Integrated
Modbus -
stop bit
R/W Encoded 00: 1 bit
01: 2 bits (default setting)
–