EasyManua.ls Logo

Eaton PXR10 - Page 58

Eaton PXR10
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 Modbus RTU – integrated Modbus port specification
9.3 Modbus register map
54 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
404851 406387 12F2 18F2 Minimum value - I
L1
(IA) A 10
404853 406389 12F4 18F4 Maximum value - I
L1
(IA) A 10
404855 406391 12F6 18F6 Minimum value - I
L2
(IB) A 10
404857 406393 12F8 18F8 Maximum value - I
L2
(IB) A 10
404859 406395 12FA 18FA Minimum value - I
L3
(IC) A 10
404861 406397 12FC 18FC Maximum value - I
L3
(IC) A 10
404863 406399 12FE 18FE Minimum value - I
G
(IG) A 10
404865 406401 1300 1900 Maximum value - I
G
(IG) A 10
404867 406403 1302 1902 Minimum value - I
N
(IN) A 10
404869 406405 1304 1904 Maximum value - I
N
(IN) A 10
404871 406407 1306 1906 Minimum value - U
L1
(VA) V 10
404873 406409 1308 1908 Maximum value - U
L1
(VA) V 10
404875 406411 130A 190A Minimum value - U
L2
(VB) V 10
404877 406413 130C 190C Maximum value - U
L2
(VB) V 10
404879 406415 130E 190E Minimum value - U
L3
(VC) V 10
404881 406417 1310 1910 Maximum value - U
L3
(VC) V 10
404883 406419 1312 1912 Minimum value - U
L1-N
(VAN) V 10
404885 406421 1314 1914 Maximum value - U
L1-N
(VAN) V 10
404887 406423 1316 1916 Minimum value - U
L2-N
(VAN) V 10
404889 406425 1318 1918 Maximum value - U
L2-N
(VAN) V 10
404891 406427 131A 191A Minimum value - U
L3-N
(VAN) V 10
404893 406429 131C 191C Maximum value - U
L3-N
(VAN) V 10
404895 406431 131E 191E Overload pre-warning % 1
404959 406495 135E 195E Counter - I
sd
, I
i
tripping 1
404961 406497 1360 1960 Counter - I
r
, I
g
tripping 1
404963 406499 1362 1962 Operations counter 1
404965 406501 1364 1964 Counter - I
sd
tripping 1
404967 406503 1366 1966 Counter - I
i
tripping 1
404969 406505 1368 1968 Counter - bypass tripping 1
404971 406507 136A 196A Counter - I
r
tripping 1
404973 406509 136C 196C Counter - I
g
tripping 1
404975 406511 136E 196E Counter - trips total 1
404977 406513 1370 1970 Counter - test mode tripping 1
404979 406515 1372 1972 Counter - number of openings via the
communication interface
1
Register number Register address
(HEX)
Object
IEEE floating
point
Fixed point
(FP)
IEEE floating
point
Fixed point
(FP)
Description
(Values in brackets reflect the
American notation.)
Unit
Scale
factor (FP)

Table of Contents