9 Modbus RTU – integrated Modbus port specification
9.3 Modbus register map
70 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Table 32: Minor alarm event
408217
Unsigned 32 R I
L1
/ IA A
408219 Unsigned 32 R I
L2
/ IB A
408221 Unsigned 32 R I
L3
/ IC A
408223 Unsigned 32 R I
N
/ IN A
408227 Unsigned 32 R I
G
/ IG residual A
408229 Unsigned 16 R U
L1-L2
(VAB) V
408230 Unsigned 16 R U
L2-L3
(VBC) V
408231 Unsigned 16 R U
L3-L1
(VCA) V
408232 Unsigned 16 R U
L1-N
(VAN) V
408233 Unsigned 16 R U
L2-N
(VBN) V
408234
Unsigned 16 R U
L3-N
(VCN) V
408235
Signed 32 R Active 3-phase power W
408237 Signed 32 R Reactive 3-phase power VAR
408239 Unsigned 32 R Apparent 3-phase power VA
408241 Signed 32 R Active power demand W
408243 Signed 32 R Reactive power demand VAR
408245 Unsigned 32 R Apparent power demand VA
408248 Unsigned 32 R Frequency 1/10 Hz
408250 Unsigned 32 R Number of operations –
408251 Bit 31 - Bit 0 R Binary status with valid bits –
Register
number
Format R/W Description
408193 Encoded R/W Event type
summary = 0x81FF
408194
Signed 32 R Earliest event ID
408196
Signed 32 R Latest event ID
408198 Signed 32 R/W Requested event ID
408200 Signed 32 R Previous event ID
408202
Signed 32 R Next event ID
408204
Date/time R Date/time
408212 Encoded R Data format
Small alarm: 0x0006
408213
Bit 0 R Valid bits of the object
408214
Encoded R Status reason (primary, secondary, reason code)
Register
number
Format R/W Description Unit