10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.1 EtherNet/IP
86 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Table 48: Real-time data register - EtherNet/IP
Instance
Object
IEEE
floating
point
Fixed
point (FP)
Description
(Values in brackets reflect the American
notation.)
Unit Scale
factor (FP)
56 182 Cause of status:
High byte = primary status
Low byte = secondary status
– –
57
183 I
L1
(IA) A 10
58
184 I
L2
(IB) A 10
59 185 IL3 (IC) A 10
60 186 I
G
(IG) A 10
61
187 I
N
( IN) A 10
62
188 U
L1-L2
(VAB) V 10
63 189 U
L2-L3
(VBC) V 10
64 190 U
L3-L1
(VCA) V 10
65 191 U
L1-N
(VAN) V 10
66 192 U
L2-N
(VBN) V 10
67 193 U
L3-N
(VCN) V 10
72 198 Active 3-phase power W 1
73 199 Reactive 3-phase power Var 1
74
200 Apparent 3-phase power VA 1
75 201 Power factor – 100
76 202 Frequency Hz 10
81 207 Peak active power demand W 1
82 208 Product ID – –
83 209 Frequency Hz 100
– 210 Active energy (forward) kWh 1
–
211 Active energy (reverse) kWh 1
–
212 Active energy combined (= forward + reverse) kWh 1
–
213 Apparent energy kVAh 1
–
214 Active energy (forward) Wh 1
–
215 Active energy (reverse) Wh 1
–
216 Active energy combined (= forward + reverse) Wh 1
–
217 Apparent energy VAh 1
84 218 Peak reactive power demand Var 1
85 219 Peak apparent power demand VA 1
90
224 Active power demand W 1
91 225 Reactive power demand Var 1
92
226 Apparent power demand VA 1