10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.1 EtherNet/IP
92 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Table 49: Setting group 0: “System group” - EtherNet/IP
Instance
Bit
field
Mask
field
Setpoint name R/W Format Description or value Unit
2 15 - 0 Password W – 0000 (default setting –
3 15 - 0 0xFFFFFF Group 0 = system R/W – 0x00FF –
4
12 - 0 0x1FFFF Rated current R Encoded NZM2: 25, 40, 63, 90, 100, 140, 160, 200, 220,
250, 300
NZM3: 250, 350, 400, 450, 600, 630
NZM4: 550, 600, 630, 800, 875, 1000, 1200, 1250,
1400, 1600
A
5
2 - 0 0x0007 Frame size R Encoded The frame size indicates the breaker type
11: NZM2
12: NZM3
13: NZM4
–
6
3 - 0 0x000F Trip type version -
part 1
R Encoded Bit 0: LdSel: with overload protection I
r
= 1
Bit 1: SdSel: with short-time delayed short-circuit
protection I
sd
= 1
Bit 2: InstSel: with instantaneous short-circuit
release I
i
= 1
Bit 3: GfSel: with ground-fault protection I
g
= 1
Bit 4: ARMSel: with maintenance mode = 1
Bit 5: OvrideSel: with instantaneous release
function = 1
Bit 6: not used
Bit 7: MotorSel: with motor-protection function
=1
Bit 8: NeuSenorSel:
0: 3-pole device
1: 4-pole device
Bit 9: ThermalSel: with thermal memory = 1
Bit 12: VoltSel: with voltage meter = 1
Bit 13:
0: PXR20
1: PXR25
–
7
Trip type version -
part 2
R Encoded Bit 0: ModbusSel: with integrated Modbus RTU
=1
Bit 1: CAMSel: with CAM RS422 = 1
Bit 2: IOModuleSel: with IO module = 1
Bit 3: RelaySel: with relay module = 1
Bit 4: ZSISel: with zone selectivity = 1
Bit 12: NZM_ACB_Sel: degree of protection
0: IZMX
1: NZM
Bit 13: IECSel:
0: UL
1: Standard IEC
Bit 0: ModbusSel: with integrated Modbus RTU
=1
Bit 1: CAMSel: with CAM RS422 = 1
Bit 2: IOModuleSel: with IO module = 1
Bit 3: RelaySel: with relay module = 1
Bit 4: ZSISel: with zone selectivity = 1
Bit 12: NZM_ACB_Sel: degree of protection
0: IZMX
1: NZM
Bit 13: IECSel:
0: UL
1: Standard IEC
–