XS series operating manual 
 
XS user manual v0.55  - 136 - 
Dielectric strength tests 
 
The  dielectric  strength  test  is  intended  to  stress  components  and  sub-assemblies  of  electrical 
equipments and to check that the leakage lines either between points or between points and ground are 
correctly designed according to the used technology. 
The principle of a dielectric strength test is to apply a voltage (DC or AC) between defined points and 
after  voltage  stabilization,  to  check  that  the  leakage  current,  created  by  breakdown  phenomena  or 
breakdown  discharges  (in  the  air  or  in  the  insulating  materials),  is  not  greater  than  the  nominal 
acceptable value. 
The default sanction is determined by the analyze of the shape, the amplitude and the holding time of 
the current supplied by the generator to the specimen under test and by comparison with a preset limit. 
 
 
Selection of the test voltage 
 
The  dielectric  strength  tests  intending  to  verify  that  materials  or  equipments  comply  with  standard 
requirements, it is important to refer to these standards to select the voltage.  
In case of no indication regarding the test voltage, a common rule is to apply the following formula : 
Utest = 2 x Unominal + 1000 volts 
Most of the standards specify the type of the test voltage : AC (50-60Hz) or DC. A common rule is to test 
the specimen with a test voltage of the same type that the voltage which will be apply during the final 
use. However, certain among of technical difficulties exist which force to depart from this common rule. 
 
Dielectric strength tests with an ac voltage 
 
BENEFITS : 
  The specimen is stressed with the both voltage polarities. 
  The specimen being not charged, there is no need for a discharge system 
 
DISADVANTAGES : 
  Most of the tested specimens having a certain amount of capacitance, the HV source have to supply 
the  leakage  current as  well  as  the  reactive current,  this  involves an  over-sized generator  with an 
increase  in  prices,  in  weight  and  a  decreasing  of  the  operator  safety  who  is  exposed  to  higher 
currents. 
The reactive current can be evaluated with the following formula : 
Impedance = Voltage / Current (Ohm’s law : Z=U/I) 
for capacitances : Z = 1 / Cw with w = 2*Pi*F 
reactive current : Ir = U*C*2*Pi*F 
i.e.    U=3000 volts C=1nF (~ 10 meters of shielded cable) 
    Ir=3000*1E-9*2*3.14*50=0.942 mA 
 
  Require to adjust the permanent leakage current threshold (IMAX) regarding the capacitance of each 
specimen. 
  When testing a specimen which will be used with a DC voltage, the AC voltage test can result in a 
decreasing of the life time because in particular of the heating and the CORONA effect. Under the 
effect of an electrical field, the orientation of molecules is done with friction which will occur with an 
AC voltage at each cycle (every 20 or 16 mS). Consequently the AC test is more severe than the DC 
voltage test.