3.4 Connection of station earthing
The Xiria unit can be connected either to the left or to the
right of the station earthing. An earth bar, to which the
earth screens of the power cables and the system earth
can be connected, is located at the rear of every cable
connection compartment.
See Figure 3-12.
The earth bar is provided with 10 mm holes on both ends
outside the unit for the connection of the system earth.
Three M8 nuts are mounted on the earth bar in each cable
compartment for the connection of the earth screens of the
power cables.
3.5 Access to secondary compartment
The front plate requires to be removed in order to gain
access to the secondary compartment.
Procedure (standard)
1. Remove the screws at the bottom of the front plate,
see Figure 3-13.
2. Move the bottom of the front plate forward, lower it
and remove it, see Figure 3-14.
3. The secondary compartment is now accessible.
Figure 3-12: Earth bar
Figure 3-13: Position of front plate fixing screws
Figure 3-14: Removing the front plate