----------------------630-----------------------------------
Rated short-time withstand current
Rated short time withstand current alternative
Rated peak withstand current
---------------------200/500/630-------------------------
Rated short-circuit making current
Rated Capacitive Switching Current Class
----------------------C2-------------------------------------
Rated Cable Charging Breaking Current
----------------------31.5-----------------------------------
----------------------45--------------------------------------
----------------------<20------------------------------------
Mechanical Endurance Class
-----------------------M1------------------------------------
Mechanical Endurance Class as Earth Switch
-----------------------M1------------------------------------
Mechanical Endurance Class Disconnector
-----------------------M0------------------------------------
Electrical Endurance Class
-----------------------E2-------------------------------------
Electrische classificatie als aardingsschakelaar
-----------------------E2-------------------------------------
Rated short-time withstand current
Rated short-time withstand current alternative
----------------------80-------------------------------------
----------- O - 3 min - CO -3 min - CO --------------
-----------------------630-----------------------------------
Rated active load break current
-----------------------630-----------------------------------
Rated short-circuit making current
Rated short-time withstand current
Rated short-time withstand current alternative
Rated Cable Charging Breaking Current
----------------------31.5-----------------------------------
Mechanical Endurance Class
--------------------M2 5000x------------------------------
Mechanical Endurance Class as Earth Switch
-----------------------M0------------------------------------
Mechanical Endurance Class Disconnector
-----------------------M0------------------------------------
Electrical Endurance Class
-----------------------E3-------------------------------------
Electrical Endurance Class as Earth Switch
-----------------------E2-------------------------------------
Standard auxiliary voltage
---------------------24 V DC--------------------------------
Auxiliary voltage with voltage converter
---------36-72 V DC & 36-60 V AC --------------------
-------100-353 V DC & 100-240 V AC ---------------
Auxiliary voltage tolerances
------------------- +10% -30% ----------------------------
Watt losses controller K7
----5 W continuous when idle -------------------------
Power supply for closing motor
--------------55 W 15 seconds-------------------------
Power supply for trip coil
-----------------40 W 100 msec.-------------------------