Xiria
8
994.570 G01 06
Busbar system:
Rated normal current
A
----------------------630-----------------------------------
Rated short-time withstand current
kA-s
20-1
20-1
20-1
20-1
20-1
Rated short time withstand current alternative
kA-s
20-3
20-3
20-3
20-3
20-3
Rated peak withstand current
kA
50
50
50
50
50
Circuit-breakers:
Rated normal current
A
---------------------200/500/630-------------------------
Rated breaking current
kA
20
20
20
20
20
Rated short-circuit making current
kA
50
50
50
50
50
Rated Capacitive Switching Current Class
----------------------C2-------------------------------------
Rated Cable Charging Breaking Current
A
----------------------31.5-----------------------------------
DC Time Constant
msec
----------------------45--------------------------------------
DC Component
%
----------------------<20------------------------------------
Mechanical Endurance Class
-----------------------M1------------------------------------
Mechanical Endurance Class as Earth Switch
-----------------------M1------------------------------------
Mechanical Endurance Class Disconnector
-----------------------M0------------------------------------
Electrical Endurance Class
-----------------------E2-------------------------------------
Electrische classificatie als aardingsschakelaar
-----------------------E2-------------------------------------
Rated short-time withstand current
kA
20-1
20-1
20-1
20-1
20-1
Rated short-time withstand current alternative
kA
20-3
20-3
20-3
20-3
20-3
Minimum tripping time
msec
----------------------80-------------------------------------
Mechanism type
----------- O - 3 min - CO -3 min - CO --------------
Load break switches:
Rated normal current
A
-----------------------630-----------------------------------
Rated active load break current
A
-----------------------630-----------------------------------
Rated short-circuit making current
kA
50
50
50
50
50
Rated short-time withstand current
kA-s
20-1
20-1
20-1
20-1
20-1
Rated short-time withstand current alternative
kA-s
20-3
20-3
20-3
20-3
20-3
Rated Cable Charging Breaking Current
A
----------------------31.5-----------------------------------
Mechanical Endurance Class
--------------------M2 5000x------------------------------
Mechanical Endurance Class as Earth Switch
-----------------------M0------------------------------------
Mechanical Endurance Class Disconnector
-----------------------M0------------------------------------
Electrical Endurance Class
-----------------------E3-------------------------------------
Electrical Endurance Class as Earth Switch
-----------------------E2-------------------------------------
Remote control options:
Standard auxiliary voltage
---------------------24 V DC--------------------------------
Auxiliary voltage with voltage converter
---------36-72 V DC & 36-60 V AC --------------------
-------100-353 V DC & 100-240 V AC ---------------
Auxiliary voltage tolerances
------------------- +10% -30% ----------------------------
Watt losses controller K7
----5 W continuous when idle -------------------------
Power supply for closing motor
--------------55 W 15 seconds-------------------------
Power supply for trip coil
-----------------40 W 100 msec.-------------------------