SDi Decades Extreme Service Manual www.ecoer.com
May. 2023Manufacturer reserves the right to change specifications or designs without notice.
8.7.16 EC 72 (Lack phase failure of outdoor DC fan motor diagnosis and solution)
Description: When the three-phase sampling current of the DC motor is abnormal, especially when the current
of one or more phases is always small and almost 0, the LED displays the failure code.
Recommended parts to prepare:
Connection wire
Fan motor
Outdoor PCB
Troubleshooting and repair:
Check the fan three-phase
output for obvious open circuit
Power off,then restart the unit
2 minutes later.Is it still
displaying the error code
The unit operates
normally
Check the wiring of fan
motor.Are all the connections
good?
Correct the connections
Check whether the three-
phase resistance of the fan
is symmetrical
Replace the fan motor
Yes
Yes
Yes
No
Replace the main PCB
No
Trobule is solved
Yes
No
No