The unit enters defrosting mode according to the temperature value of T3 and T4 as well as the
compressor running time.
In defrosting mode, the compressor continues to run, the indoor and outdoor motor will cease operation, the
defrost light of the indoor unit will turn on, and the symbol is displayed.
If any one of the following conditions is satisfied, defrosting ends and the machine switches to normal
heating mode:
T3 rises above TCDE1.
T3 maintained above TCDE2 for 80 seconds.
Unit runs for 15 minutes consecutively in defrosting mode.
If T4 is lower than or equal to -8 and compressor running time is more than TIMING_DEFROST_TIME, if
any one of the following conditions is satisfied, defrosting ends and the machine switches to normal heating
mode:
Unit runs for 10 minutes consecutively in defrosting mode.
T3 rises above 50.
3.4.5 Evaporator Coil Temperature Protection
When the evaporator temperature exceeds a preset protection value, the compressor stops operation.
7.3.5 Auto Mode
This mode can be selected with the remote controller and the temperature setting can be adjusted between
60~86.
In auto mode, the u n i t selects cooling, heating, or
fan-only mode on the basis of T (T =T1-TS).
∆T
Running mode
∆T>4
Cooling
-6<∆T≤4
Fan-only
T≤-6
Heating*
Heating*: In auto mode, cooling only models run the fan
Indoor fan will run at auto fan speed.
If the machine switches mode between heating and cooling, the compressor will keep stopping for
certain time and then choose mode according to T.
7.3.4.4 Defrosting mode
Note: TCDE1, TCDE2 are the parameters of of EEPROM.
7.3.6 Dry Mode
In drying mode, AC operates the same as auto fan in cooling mode.
All protections are activated and operate the same as they do that in cooling mode.
Low Room Temperature Protection
If the room temperature is lower than 50, the compressor ceases operations and does not resume until room
temperature exceeds 54.
7.3.4.3 Outdoor Fan Control:
The outdoor unit will be run at different fan speed according to T4 and compressor frequency.
For different outdoor units, the fan speeds are different.