INSTRUCTION MANUAL ECOSOFT RO SYSTEM
MO6500BWTSS
Pushing STOP will bring the controller to Stop mode. Pushing START will take the controller
into Service if permeate is low and backpressure switch is inacve. Otherwise, pushing START
will iniate Forward Flush 1 and Forward Flush 2 (if set) and then bring the controller back to
Standby. When oat switch or permeate backpressure switch deacvate, the controller will go back
to Service.
FAULT
In Fault mode, the unit is stalled to protect the equipment from dangerous operang condions.
Fault mode is brought on by acvang low feed pressure switch (to prevent ‘dry running’), high
feed pressure switch (to protect against overpressure), or reading an excessively high permeate
conducvity value (which could mean membrane rupture or other malfuncon if conguraon
step 1.16 is set to non-zero value.).
Fault mode can only be quit manually by pushing START. Ensure the cause of fault is eliminated
before quing Fault mode. Pushing STOP will bring the controller to Stop mode.
STOP
In Stop mode, the unit is stalled and awaing further input. Stop mode can be manually brought
on by pushing STOP in any mode, or by stop switch opening circuit between STOP terminals on
the printed circuit board.
Upon pushing START or deacvang stop switch, the controller will resume from where it was
interrupted.
Status of outputs in FAULT
Booster and anscalant pumps o
Entry valve closed
Forward ush valve closed
Bypass valve closed
Alarm on
Status of outputs in STOP
Booster and anscalant pumps o
Entry valve closed
Forward ush valve closed
Bypass valve closed
Alarm o