EasyManua.ls Logo

Edwards TCU 40/80

Edwards TCU 40/80
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.
Press
MUTE
to
silence
the
alarm.
The
TCU
40/80
is
shipped
without
coolant.
The
coolant
level
alarm
will
sound
and
the
front
panel
Reservoir
Coolant
Low
Level
LED
will
be
red
indicating
that
the
reservoir
must
be
filled.
5.
Fill
the
coolant
reservoir
using
the
procedure
Filling
the
Reservoir
on page
26.
6.
Press
the
START
button
and
verify
the
front
panel
indicators
are
as
in
the
Start
Condition
column
of
Table
8.
7.
Use
a
halogen
leak detector
to
check
all
supply
and
return
line
connections
at
both
the
TCU
and
process
equipment,
around
the
pump
head
assembly,
drain
valve,
heater,
flow
switch,
vent
line,
fill
line,
and
reservoir
pressure
relief
valve.
6.3
Changing
the
setpoint
value
(SV1)
The
following
instructions
are
for
local
temperature
control
only.
Do
not
exceed
the
temperature
range
of-40
°C
to
+80
This
is
the
normal
operating
range
of
the
TCU
40/80.
To
change
the
temperature
settings
press
page
up
or
page
down
to
cither
increase
or
decrease
the
temperature.
The
red
display
"PV"
indicates
the
process
value.
The
green
display
"SP"
indicates
the
current
setpoint.
Note:
The
temperature
controller
has
been
programmed
to
prevent
the
setpoint
from
exceeding
the
normal
operating
range
of
the
TCU
40/80.
The
controller
is
also
protected
from
unauthorized
changes
to
the
Pid
and
other
settings,
Contact
the
process
equipment
supplier
for
access
to
these
settings
and
other
information.
'P
EDWARDS
0UT1O
OUT
tO
OUH.
F
-j
-71
-■
HUBI
MB
4
:
mb
Figure
10
-
Temperature
controller
6.4
Temperature
controller
Pid
settings
Edwards
default
settings
are:
PID1
-
heating
Pbl
Arl
rAtl
dbl
value
8.0
0.43
7.0
1.0
PID2
-
cooling
Pb2
Ar2
rAt2
db2
value
12.5
0.7
9.0
1.0
parameter
proportional
band
automatic
reset
rate
deadband
TCU
40/80
Temperature
Control
Unit
21

Related product manuals