USV MT3200 Instruction manual
MT Series
Page 18 of 36
8 Installing and connecting the UPS
All requirements in the technical data regarding environmental and operating
conditions must be observed to ensure trouble-free functioning of the UPS.
The following must be observed when setting up / installing the UPS
equipment:
o Avoid extremes of temperature and atmospheric humidity. A maximum
service life, particularly in relation to the batteries, is achieved at an
ambient temperature of 15-25°C.
o Always ensure that sufficient space is available behind the UPS to
make the necessary connections and, as the UPS is heavy, use
suitable guide rails during installation. The load-bearing capacity of the
support must be sufficient.
o Observe the specified installation location and only mount the
equipment using the screw-in positions shown.
o Make sure that ventilation of the equipment is possible at all times. As
this UPS is ventilated in a crosswise and lengthwise direction, a
minimum clearance of at least 50mm between the UPS and the cabinet
in which it is installed must be maintained at the sides as well as at the
front and back. Ensure an appropriate flow channel.
o Make sure the equipment is arranged correctly. When installed in
parent systems (e.g. machine, control cabinet), it must be ensured that
the UPS operates within the specified temperature range. A sufficient
level of forced ventilation must exist to remove excess heat that builds
up in the space where the UPS is installed.