USV MT3200 Instruction manual
MT Series
Page 34 of 36
14 Technical Data
14.1 Equipment specifications
Model: MT3200
Power: 3200 VA / 2000 W
Mains power
input:
Phases 1 phase conductor + neutral conductor
Input range 171 – 278 V AC
Rated frequency 50 / 60 Hz
Synchronous range 45 – 65 Hz
Boost (+13%) yes
Buck (-13%) yes
UPS output: Transfer voltage (on-
line mode)
200 – 250 V AC
Rated voltage (support
mode)
230 V AC
(sine +/-6%)
Max. output current 13,9 A
Overload capacity [110 ... 130 %]: 10 – 25 s, > 130 % 1,5 s
Bridging time approx. 8 min under rated conditions
Efficiency: AC -> AC > 95 %
DC input Input voltage 48V DC (rated)
Interface: LAN / RS232 9-pin D-SUB jack
(galvanically isolated)
Environmental
data:
Perm. temp. range 0 ... + 40 °C
Recommended temp. +15 ...+ 25 °C
Storage temperature 0 ... +40 °C
Rel. atmos. humidity 0 ... 90% (non-condensing)
Normen: EN 50091-1, EN 50091-2
General Cooling Fan cooling
Noise level < 45 dB
Weight 43 kg
Inspections TÜV / GS / CE
Dimensions H x W x D [mm] 290 x 160 x 530 mm