EasyManua.ls Logo

Effekta MT 3200 - Page 23

Effekta MT 3200
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
USV MT3200 Instruction manual
MT Series
Page 23 of 36
Support mode:
If the mains power fails, the UPS immediately switches to support mode.
Display/alarm signal: support mode is indicated by the illumination of the ON
Bat” display and the load at the output (here 50% by way of example).
Sequence (A) is used as the audible alarm signal.
Overload mode:
If the UPS output is overloaded, the UPS switches off after a short time interval
(approx. 20 seconds). The UPS switches off immediately in the event of a short
circuit on the output side.
Display/alarm signal: overload mode is indicated by illumination of the 100%
output load indicator. Sequence (C) is used as the audible alarm signal. In
addition, the “ON Line” indicator here shows available mains power.
Test mode:
If the UPS is in on-line mode, test mode can be initiated by pressing the “TEST”
button.
Display/alarm signal: the display (including the alarm signal) is the same as in
support mode, although mains power is available.

Related product manuals