EasyManua.ls Logo

electroil Archimede IMMP2.2W-BC - 6.5 Alarms

Default Icon
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
ARCHIMEDE LCD SERIES - ENG
ELECTROIL
Pressure Control
1. Pressure Hysteresis [BAR]
2. Max Limit Pressure [%]
3. Dry working stop delay [s]
4. Dry working re-start delay time
[min]
5. Minimum flow stop delay [s]
6. Re-start delay after minimum flow
stop [s]
7. Cos φ limit
8. Alternation time
1. Pressure control hysteresis- Default: 0.20 BAR;
2. Max value of pressure % referred to Set-point
pressure value – Default: 130% (increase the value
up to 200% in case of alarm 14 “Max Pressure”);
3. Dry working stop delay time for pump filling– Default:
40 seconds;
4. Dry working re-start delay time after firsts 4th try;
after the 5th try the Inverter stop with manual re-start
(STOP + START)– Default: 15 minutes;
5. Delay time before minimum flow stop – Default: 15
second;
6. Re-start delay time after minimum flow stop -Default:
1 second;
7. When cos φ go down this value the pump stop for
dry working (may be absence of input water or air) –
Default: 0.5;
8. Alternation time on the change from one to other
pump to define the first to start
Group Functioning
1. Control type
Pump Speed
Pump Pressure
MasterSlave
2. Reference speed [RPM]
3. Pumps number (2..8)
4. Code (0..7)
5. Radio Frequency (780..820 MHz)
6. Stand-by preheating temperature
1. Set Control Type (Default: Pump Pressure):
Pump speed: directly regulation of the speed in
absence of pressure sensor; security stop for null
flow and dry working conditions, only with manually
re-start.
Pump pressure: feedback control of pressure - need
the pressure sensor;
MasterSlave – group functioning with others Inverters
2. Value of the reference speed on the Speed control;
3. Pumps Number: Number of pumps in group
functioning (2..8).
4. Code: 0 for Master; >=1 for Slave
5. Radio Frequency: communication R/T frequency
(must be the same for the inverters on the group)
6. Minimum preheating temperature with the engine
stopped – Default: 25°C (the function can be
deactivated by setting the relevant parameter to 0)
P.I.D. factors
1. K
proportional
2. K
integral
3. Pressure ramp
1. K
proportional
: 0-100. Pressure error multiplayer –
Default: 25
2. K
integral
: 0-100. Integral of pressure error
multiplier - Default:25
3. Pressure ramp [bar/s]: 0.1-10.00 – Default: 0.5
BAR/s
Alarm history
Alarm N°
Type
Visualization of last 100 alarm events (see table 7) in
chronologic order.
Table 6: advanced functions sub-menu
6.5 Alarms
Alarm
Alarm Type Description
1
Current Peak
Immediately stop probably caused by short-circuit
Automatic re-start; final stop after 10 consecutive events
2
Over-Voltage
Normally caused by over voltage pick supply. Automatic re-start; final stop after 10
consecutive events
3
Inverter Temperature
Over temperature IGBT protection (90°C)
Automatic re-start; final stop after 10 consecutive events
4
Thermal protection
Motor thermal protection related to nominal current set, for motor insulations saving at high
temperatures. Automatic re-start; final stop after 10 consecutive events
5
Dry operating
Null input flow or air presence;
Automatic re-start; final stop after 5 consecutive events
6
Pressure sensor problem
Pressure sensor output problem
Automatic re-start; final stop after 10 consecutive events
7 Under-Voltage
Input voltage under the minimum working limit.
Automatic re-start; final stop after 10 consecutive events
8 Enable OFF
Open contact between EN e C (figure 14-15-16): stop the motor; the motor restart when
the contact will close again
9 Over-Current IGBT
Over current on the IGBT, overtaking a current limit value setting
Automatic re-start; final stop after 10 consecutive events
10 INPUT-OUTPUT
inverted
Connection mistake: Voltage supply connected on the output and Motor cable connected
on the entrance: reverse in order to enable the motor

Related product manuals