ARCHIMEDE LCD SERIES - ENG
ELECTROIL
FUNCTIONS MENU DESCRIPTION
Main Menu
Submenu
Description
Lingua/Language Italian, English, French, Spanish, Czech
Insert language for display LCD
Default: Italiano
Reference Pressure
Reference pressure
[X.X BAR]
Pressure followed in feedback through pressure
sensor.
The same parameter can change directly during
pump functioning, pushing “+” or “-“ on the control
panel. Default: 3.0 BAR
Motor data
(PASSWORD required)
1. Nominal Voltage [V]
2. Nominal frequency [Hz]
3. Current absorbed [A]
4. Rotation (only for IMTP-ITTP)
5. Minimum flow power stop [%]
6. Dry working power stop [%]
1. Nominal motor Voltage – Default: 230V for
IMMP-IMTP; 400V for ITTP models;
2. Nominal Motor frequency – Default: 50Hz;
3. Set the motor current reading by motor rating
data, according to the motor phases connection in
use (star/triangle, see 5.3).
4. Set the rotation direction (0/1) – Default: 0;
5. Fine regulation of the minimum flow power stop
value referring to the value stored during check
(regulation from 80% to 120%, default: 102%)
6. Regulation of the dry working stop value
referring to the value stored during check
(regulation from 50% to 100%, default: 80%)
Pump data
(PASSWORD required)
Maximum Pressure [BAR]
Self regulation Check [ON-STANDARD /
ACCURATE / OFF]
Maximum pressure limitation –
Default: 10.0 BAR
With Check on ON or STANDARD or ACCURATE
mode at the next START will start the self
regulation check.
STANDARD CHECK procedure: fast (approx. 2
minutes) –closing totally the delivery side of the
pump;
ACCURATE CHECK procedure (available only for
IMMP1.1 / 1.8 / 2.2W-BC): Slow mode (approx. 4-
5 minutes) with better accuracy on respect the
standard mode; Attention: opening the delivery a
little, leaving the minimum flow value required for
the minimum flow protection stop. Follow the
instructions showed on the LCD display during the
check.
Sensor data
(PASSWORD required)
1. MIN [ mA; V]
2. MAX [ mA; V]
3. Range [BAR]
1. MIN: minimum output value pressure
sensor – Default: 4.0 mA – 1.0V;
2. MAX: maximum output value pressure
sensor – Default: 20 mA – 5.0 V;
3. Range: measure range of pressure
sensor – Default: 16 BAR;
Advanced functions
(PASSWORD required)
Enter to advanced functions
To enter to advanced functions for advanced
regulations (see table 6).
Data Saving
Saving data modified or Reset
constructor data
Yes: save modify
No: back to previus data
RESET: reset constructor data
Table 5: Main Menu description
ADVANCED
FUNCTIONS MENU
Sub
-
menu
ADVANCED FUNCTIONS
Description
Motor Limits
1. Maximum velocity [%]
2. Minimum velocity [%]
3. Acceleration [RPM/s]
4. Deceleration [RPM/s]
5. Maximum current [%]
6. Starting motor frequency [Hz] (only
for IMMP models)
7. Starting motor current [A] (only for
IMMP models)
1. Maximum Motor Velocity – Default: 100%;
2. Minimum Motor Velocity – Default:50%;
3. Motor acceleration – Default: 3s;
4. Motor deceleration – Default 3s
5. Maximum Motor current limit– Default: 100%
6. Starting frequency (speed) for single-phase motor –
Default: 45Hz
7. Starting current for single phase motor - Default: 28
Ampere.
Values % on respect the nominal values