l
IPd must be higher than S S P + Sd.
l
IPd must be higher than dtd.
l
dtd must be higher than S P + dIF.
l
SSP must be higher than S P.
l
dtt must be lower than S P.
9.4 Celsius or Fahrenheit (CF)
The table below details the Celsius or Fahrenheit parameter (CF).
Display
Description Option to set the EMS controller to Celsius (°C) or Fahrenheit (°F).
Considerations
l A global reset sets EMS controllers using Fahrenheit (°F) to Celsius C).
l Applies to alltemperature settings and values.
l
May not appear in allOFCfirmware
Range 00 (°C) or 01 (°F)
Global default 00 (°C)
9.5 Set point (SPC or SPF)
The table below details the set point (SPC or SPF) parameter.
Display
Description
Defines the compressor cut-out temperature during the ready mode. The set
point (SP) temperature is the lowest measured temperature under normal
operating conditions.
The set point is displayed as SPC (set point Celsius) or SPF (set point Fahren-
heit) depending on whether the EMS controller is set to use Celsius or Fahren-
heit.
Considerations Must be above the freeze-up protection (dtt) temperature.
Range -9.9 to 9.9°C (14 to 50°F)
Global default
3.0°C (37°F)
ems75sz: -3.0°C (27°F)
9.6 Differential (dIF)
The table below details the differential (dIF) parameter.
67 of 86
27 February 2014