6 Functionality Description
26 User’s Guide Smartpack Monitoring & Ctrl Unit,
350003.013, v5-2006-11
The table shows an example of values entered in the Battery Lifetime Temperature
monitor.
Temperature Range Time within Range
Range # Low Limit, °C High Limit, °C Hours
01 00 10 10
02 11 20 20
03 21 30 60
04 31 40 40
05 41 50 05
06 51 60 00
07 61 65 00
08 66 70 00
09 71 75 00
10 76 99 00
You can reset the values in the Battery Lifetime Temperature monitor either by selecting
ServiceOption>BattLifeTime Rst”, via the Smartpack controller’s front keys, or using
PowerSuite.
Display Battery Information
UO (BatteryInfo)
You can display information about the power system’s battery bank by selecting
UserOption>Battery Info, via the Smartpack controller’s front keys.
Following data may be displayed selecting the Battery Info sub options (level 3):
Option Description
NoOfString Nn Number of battery strings
BattStringCurr Each battery string’s current
BattStringTemp Temperature of each battery string
BattBlockVolt Voltage of each battery block
For battery terminology, refer to chapter “About Battery Banks, Strings and Blocks”,
page 26 and to the “Quick Start Guide Flatpack2 PS System”, Art. 356804.103.
About Battery Banks, Strings and Blocks
Normally, battery banks are implemented by
connecting in parallel several battery strings; each
string is formed by battery blocks connected in series.
Figure 20 Example of a 48V battery bank
implemented with two 48V battery strings; each
string consists of four 12V battery blocks
48V Batter
y
Bank
Batter
y
String #1
(48V)
Batter
y
Block (12V)
Batter
y
String #2
(48V)